The following two images show configurations for when the condensing unit is mounted above
and below the holding plates. The check valve can be mounted to flow upward (pointed up) or
horizontally, not downward. When the condensing unit is above the plates, p-traps are installed
in each holding plate zone to get the oil to flow upward. If you have a long horizontal suction
tubing run, including u-traps every eight (8) feet will aid in oil return. U-traps are necessary when
you have a slight incline in a long horizontal run. In the images below, notice the check valves
(arrows pointing away from plates towards condensing unit), p-traps, and u-traps.
Condensing Unit Above Plates
Page 21